{"id":582403,"date":"2026-10-21T11:16:54","date_gmt":"2026-10-21T01:16:54","guid":{"rendered":"https:\/\/www.vibewire.com.au\/?p=582403"},"modified":"2026-10-21T11:16:58","modified_gmt":"2026-10-21T01:16:58","slug":"in-virginia-a-data-center-ran-diesel-generators-during-a-code-red-alert","status":"publish","type":"post","link":"https:\/\/www.vibewire.com.au\/?p=582403","title":{"rendered":"In Virginia, a data center ran diesel generators during a Code Red alert"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">At Vantage Data Centers&#8217; VA2 campus in Sterling, eight on-site natural-gas turbines supply electricity instead of the electric grid. During a July incident, the turbine plant failed, and dozens of diesel backup generators kicked in under an emergency exemption in the facility&#8217;s air permit, according to\u00a0<a href=\"https:\/\/www.instagram.com\/p\/Deafu89Nojs\/\" target=\"_blank\" rel=\"noopener\">Kaizen Executive<\/a>.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The caption on the original&nbsp;<a href=\"https:\/\/www.instagram.com\/p\/Deafu89Nojs\/\" target=\"_blank\" rel=\"noopener\">Instagram post<\/a>&nbsp;stated, &#8220;A Vantage Data Centers facility in Sterling, Virginia, ran backup diesel generators for nearly 24 hours after its on-site power plant failed during a Code Red air-quality alert.&#8221;<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The generators began operating after regional air quality had already reached Code Red levels because&nbsp;<a href=\"https:\/\/www.thecooldown.com\/tag\/wildfires\/\" target=\"_blank\" rel=\"noopener\">wildfire<\/a>&nbsp;smoke from Canada was hanging over the area.<\/p>\n\n\n\n<figure class=\"wp-block-embed aligncenter is-type-video is-provider-youtube wp-block-embed-youtube wp-embed-aspect-16-9 wp-has-aspect-ratio\"><div class=\"wp-block-embed__wrapper\">\n<iframe loading=\"lazy\" title=\"Virginia couldn&amp;apos;t stop Sterling data center&amp;apos;s 24-hour diesel generator use, regulator says\" width=\"640\" height=\"360\" src=\"https:\/\/www.youtube.com\/embed\/E1_1edtyQtk?feature=oembed\" frameborder=\"0\" allow=\"accelerometer; autoplay; clipboard-write; encrypted-media; gyroscope; picture-in-picture; web-share\" referrerpolicy=\"strict-origin-when-cross-origin\" allowfullscreen><\/iframe>\n<\/div><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">WUSA9&nbsp;<a href=\"https:\/\/www.wusa9.com\/article\/news\/investigations\/vantage-data-center-loudoun-county-air-pollution-piedmont-environmental-council\/65-ffa00add-bb5a-4b8b-8873-f28b577c6abe\" target=\"_blank\" rel=\"noopener\">reported<\/a>&nbsp;that local resident Greg Pirio said the generators started at 8:15 p.m., and by dawn, he said lung pain had driven him from his home to his daughter&#8217;s house in Vienna, about 15 miles away.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Because the incident qualified as an emergency under the permit, Virginia Department of Environmental Quality Director Michael Rolband told local officials the agency could not stop the operation under current rules. DEQ said inspectors would review the event afterward and respond only if they found the permit had been violated.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>An on-site power failure at a Vantage Data Centers campus in Sterling, Virginia, led its backup diesel generators to run for nearly a full day during a Code Red air-quality alert.<\/p>\n","protected":false},"author":90574,"featured_media":582559,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"om_disable_all_campaigns":false,"_monsterinsights_skip_tracking":false,"_uf_show_specific_survey":0,"_uf_disable_surveys":false,"footnotes":""},"categories":[12785],"tags":[11,21415,10104],"class_list":["post-582403","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-data-centre","tag-usa","tag-vantage-data-centres","tag-virginia"],"aioseo_notices":[],"aioseo_head":"\n\t\t<!-- All in One SEO Pro 5.0.3 - aioseo.com -->\n\t<meta name=\"description\" content=\"An on-site power failure at a Vantage Data Centers campus in Sterling, Virginia, led its backup diesel generators to run for nearly a full day during a Code Red air-quality alert.\" \/>\n\t<meta name=\"robots\" content=\"max-image-preview:large\" \/>\n\t<meta name=\"author\" content=\"Telco Analyst\"\/>\n\t<meta name=\"google-site-verification\" content=\"1EIWGZ5FoylKQrO3pqls-2hXlDXKIP1lffdWZCVV0V4\" \/>\n\t<link rel=\"canonical\" href=\"https:\/\/www.vibewire.com.au\/?p=582403\" \/>\n\t\t<meta name=\"generator\" content=\"All in One SEO Pro (AIOSEO) 5.0.3\" \/>\n\t\t<meta property=\"og:locale\" content=\"en_US\" \/>\n\t\t<meta property=\"og:site_name\" content=\"VibeWire Magazine - Your Alternate News Source for Transport, Politics, UFO, Paranormal, Anything\" \/>\n\t\t<meta property=\"og:type\" content=\"article\" \/>\n\t\t<meta property=\"og:title\" content=\"In Virginia, a data center ran diesel generators during a Code Red alert\" \/>\n\t\t<meta property=\"og:description\" content=\"An on-site power failure at a Vantage Data Centers campus in Sterling, Virginia, led its backup diesel generators to run for nearly a full day during a Code Red air-quality alert.\" \/>\n\t\t<meta property=\"og:url\" content=\"https:\/\/www.vibewire.com.au\/?p=582403\" \/>\n\t\t<meta property=\"og:image\" content=\"https:\/\/www.vibewire.com.au\/wp-content\/uploads\/2026\/10\/Screenshot-2026-10-21-at-12.09.19-pm.png\" \/>\n\t\t<meta property=\"og:image:secure_url\" content=\"https:\/\/www.vibewire.com.au\/wp-content\/uploads\/2026\/10\/Screenshot-2026-10-21-at-12.09.19-pm.png\" \/>\n\t\t<meta property=\"og:image:width\" content=\"1066\" \/>\n\t\t<meta property=\"og:image:height\" content=\"710\" \/>\n\t\t<meta property=\"article:published_time\" content=\"2026-10-21T01:16:54+00:00\" \/>\n\t\t<meta property=\"article:modified_time\" content=\"2026-10-21T01:16:58+00:00\" \/>\n\t\t<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n\t\t<meta name=\"twitter:site\" content=\"@VibewireCentral\" \/>\n\t\t<meta name=\"twitter:title\" content=\"In Virginia, a data center ran diesel generators during a Code Red alert\" \/>\n\t\t<meta name=\"twitter:description\" content=\"An on-site power failure at a Vantage Data Centers campus in Sterling, Virginia, led its backup diesel generators to run for nearly a full day during a Code Red air-quality alert.\" \/>\n\t\t<meta name=\"twitter:creator\" content=\"@VibewireCentral\" \/>\n\t\t<meta name=\"twitter:image\" content=\"https:\/\/www.vibewire.com.au\/wp-content\/uploads\/2026\/10\/Screenshot-2026-10-21-at-12.09.19-pm.png\" \/>\n\t\t<script type=\"application\/ld+json\" class=\"aioseo-schema\">\n\t\t\t{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"BlogPosting\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403#blogposting\",\"name\":\"In Virginia, a data center ran diesel generators during a Code Red alert\",\"headline\":\"In Virginia, a data center ran diesel generators during a Code Red alert\",\"author\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?author=90574#author\"},\"publisher\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/#organization\"},\"image\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.vibewire.com.au\\\/wp-content\\\/uploads\\\/2026\\\/10\\\/Screenshot-2026-10-21-at-12.09.19-pm.png\",\"width\":1066,\"height\":710},\"datePublished\":\"2026-10-21T11:16:54+10:00\",\"dateModified\":\"2026-10-21T11:16:58+10:00\",\"inLanguage\":\"en-AU\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403#webpage\"},\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403#webpage\"},\"articleSection\":\"Data Centre, USA, Vantage Data Centres, Virginia\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403#breadcrumblist\",\"itemListElement\":[{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/#listItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.vibewire.com.au\\\/\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?cat=12785#listItem\",\"name\":\"Data Centre\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?cat=12785#listItem\",\"position\":2,\"name\":\"Data Centre\",\"item\":\"https:\\\/\\\/www.vibewire.com.au\\\/?cat=12785\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403#listItem\",\"name\":\"In Virginia, a data center ran diesel generators during a Code Red alert\"},\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/#listItem\",\"name\":\"Home\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403#listItem\",\"position\":3,\"name\":\"In Virginia, a data center ran diesel generators during a Code Red alert\",\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?cat=12785#listItem\",\"name\":\"Data Centre\"}}]},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/#organization\",\"name\":\"VibreWire Online\",\"description\":\"Your Alternate News Source for Transport, Politics, UFO, Paranormal, Anything\",\"url\":\"https:\\\/\\\/www.vibewire.com.au\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.vibewire.com.au\\\/wp-content\\\/uploads\\\/2024\\\/02\\\/Screenshot-2024-01-07-at-2.32.21\\u202fpm.png\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403\\\/#organizationLogo\",\"width\":1028,\"height\":930},\"image\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403\\\/#organizationLogo\"},\"sameAs\":[\"https:\\\/\\\/twitter.com\\\/VibewireCentral\"]},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?author=90574#author\",\"url\":\"https:\\\/\\\/www.vibewire.com.au\\\/?author=90574\",\"name\":\"Telco Analyst\",\"image\":{\"@type\":\"ImageObject\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403#authorImage\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/223a29ff455a766a9ceca4c2dc0352aa8baef27c37eba4cf388f9d8bb7abff7e?s=96&d=mm&r=g\",\"width\":96,\"height\":96,\"caption\":\"Telco Analyst\"}},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403#webpage\",\"url\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403\",\"name\":\"In Virginia, a data center ran diesel generators during a Code Red alert\",\"description\":\"An on-site power failure at a Vantage Data Centers campus in Sterling, Virginia, led its backup diesel generators to run for nearly a full day during a Code Red air-quality alert.\",\"inLanguage\":\"en-AU\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/#website\"},\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403#breadcrumblist\"},\"author\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?author=90574#author\"},\"creator\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?author=90574#author\"},\"image\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.vibewire.com.au\\\/wp-content\\\/uploads\\\/2026\\\/10\\\/Screenshot-2026-10-21-at-12.09.19-pm.png\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403\\\/#mainImage\",\"width\":1066,\"height\":710},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/?p=582403#mainImage\"},\"datePublished\":\"2026-10-21T11:16:54+10:00\",\"dateModified\":\"2026-10-21T11:16:58+10:00\"},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/#website\",\"url\":\"https:\\\/\\\/www.vibewire.com.au\\\/\",\"name\":\"VibreWire Online\",\"description\":\"Your Alternate News Source for Transport, Politics, UFO, Paranormal, Anything\",\"inLanguage\":\"en-AU\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.vibewire.com.au\\\/#organization\"}}]}\n\t\t<\/script>\n\t\t<!-- All in One SEO Pro -->\r\n\t\t<title>In Virginia, a data center ran diesel generators during a Code Red alert<\/title>\n\n","aioseo_head_json":{"title":"In Virginia, a data center ran diesel generators during a Code Red alert","description":"An on-site power failure at a Vantage Data Centers campus in Sterling, Virginia, led its backup diesel generators to run for nearly a full day during a Code Red air-quality alert.","canonical_url":"https:\/\/www.vibewire.com.au\/?p=582403","robots":"max-image-preview:large","keywords":"","webmasterTools":{"google-site-verification":"1EIWGZ5FoylKQrO3pqls-2hXlDXKIP1lffdWZCVV0V4","miscellaneous":""},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"BlogPosting","@id":"https:\/\/www.vibewire.com.au\/?p=582403#blogposting","name":"In Virginia, a data center ran diesel generators during a Code Red alert","headline":"In Virginia, a data center ran diesel generators during a Code Red alert","author":{"@id":"https:\/\/www.vibewire.com.au\/?author=90574#author"},"publisher":{"@id":"https:\/\/www.vibewire.com.au\/#organization"},"image":{"@type":"ImageObject","url":"https:\/\/www.vibewire.com.au\/wp-content\/uploads\/2026\/10\/Screenshot-2026-10-21-at-12.09.19-pm.png","width":1066,"height":710},"datePublished":"2026-10-21T11:16:54+10:00","dateModified":"2026-10-21T11:16:58+10:00","inLanguage":"en-AU","mainEntityOfPage":{"@id":"https:\/\/www.vibewire.com.au\/?p=582403#webpage"},"isPartOf":{"@id":"https:\/\/www.vibewire.com.au\/?p=582403#webpage"},"articleSection":"Data Centre, USA, Vantage Data Centres, Virginia"},{"@type":"BreadcrumbList","@id":"https:\/\/www.vibewire.com.au\/?p=582403#breadcrumblist","itemListElement":[{"@type":"ListItem","@id":"https:\/\/www.vibewire.com.au\/#listItem","position":1,"name":"Home","item":"https:\/\/www.vibewire.com.au\/","nextItem":{"@type":"ListItem","@id":"https:\/\/www.vibewire.com.au\/?cat=12785#listItem","name":"Data Centre"}},{"@type":"ListItem","@id":"https:\/\/www.vibewire.com.au\/?cat=12785#listItem","position":2,"name":"Data Centre","item":"https:\/\/www.vibewire.com.au\/?cat=12785","nextItem":{"@type":"ListItem","@id":"https:\/\/www.vibewire.com.au\/?p=582403#listItem","name":"In Virginia, a data center ran diesel generators during a Code Red alert"},"previousItem":{"@type":"ListItem","@id":"https:\/\/www.vibewire.com.au\/#listItem","name":"Home"}},{"@type":"ListItem","@id":"https:\/\/www.vibewire.com.au\/?p=582403#listItem","position":3,"name":"In Virginia, a data center ran diesel generators during a Code Red alert","previousItem":{"@type":"ListItem","@id":"https:\/\/www.vibewire.com.au\/?cat=12785#listItem","name":"Data Centre"}}]},{"@type":"Organization","@id":"https:\/\/www.vibewire.com.au\/#organization","name":"VibreWire Online","description":"Your Alternate News Source for Transport, Politics, UFO, Paranormal, Anything","url":"https:\/\/www.vibewire.com.au\/","logo":{"@type":"ImageObject","url":"https:\/\/www.vibewire.com.au\/wp-content\/uploads\/2024\/02\/Screenshot-2024-01-07-at-2.32.21\u202fpm.png","@id":"https:\/\/www.vibewire.com.au\/?p=582403\/#organizationLogo","width":1028,"height":930},"image":{"@id":"https:\/\/www.vibewire.com.au\/?p=582403\/#organizationLogo"},"sameAs":["https:\/\/twitter.com\/VibewireCentral"]},{"@type":"Person","@id":"https:\/\/www.vibewire.com.au\/?author=90574#author","url":"https:\/\/www.vibewire.com.au\/?author=90574","name":"Telco Analyst","image":{"@type":"ImageObject","@id":"https:\/\/www.vibewire.com.au\/?p=582403#authorImage","url":"https:\/\/secure.gravatar.com\/avatar\/223a29ff455a766a9ceca4c2dc0352aa8baef27c37eba4cf388f9d8bb7abff7e?s=96&d=mm&r=g","width":96,"height":96,"caption":"Telco Analyst"}},{"@type":"WebPage","@id":"https:\/\/www.vibewire.com.au\/?p=582403#webpage","url":"https:\/\/www.vibewire.com.au\/?p=582403","name":"In Virginia, a data center ran diesel generators during a Code Red alert","description":"An on-site power failure at a Vantage Data Centers campus in Sterling, Virginia, led its backup diesel generators to run for nearly a full day during a Code Red air-quality alert.","inLanguage":"en-AU","isPartOf":{"@id":"https:\/\/www.vibewire.com.au\/#website"},"breadcrumb":{"@id":"https:\/\/www.vibewire.com.au\/?p=582403#breadcrumblist"},"author":{"@id":"https:\/\/www.vibewire.com.au\/?author=90574#author"},"creator":{"@id":"https:\/\/www.vibewire.com.au\/?author=90574#author"},"image":{"@type":"ImageObject","url":"https:\/\/www.vibewire.com.au\/wp-content\/uploads\/2026\/10\/Screenshot-2026-10-21-at-12.09.19-pm.png","@id":"https:\/\/www.vibewire.com.au\/?p=582403\/#mainImage","width":1066,"height":710},"primaryImageOfPage":{"@id":"https:\/\/www.vibewire.com.au\/?p=582403#mainImage"},"datePublished":"2026-10-21T11:16:54+10:00","dateModified":"2026-10-21T11:16:58+10:00"},{"@type":"WebSite","@id":"https:\/\/www.vibewire.com.au\/#website","url":"https:\/\/www.vibewire.com.au\/","name":"VibreWire Online","description":"Your Alternate News Source for Transport, Politics, UFO, Paranormal, Anything","inLanguage":"en-AU","publisher":{"@id":"https:\/\/www.vibewire.com.au\/#organization"}}]},"og:locale":"en_US","og:site_name":"VibeWire Magazine - Your Alternate News Source for Transport, Politics, UFO, Paranormal, Anything","og:type":"article","og:title":"In Virginia, a data center ran diesel generators during a Code Red alert","og:description":"An on-site power failure at a Vantage Data Centers campus in Sterling, Virginia, led its backup diesel generators to run for nearly a full day during a Code Red air-quality alert.","og:url":"https:\/\/www.vibewire.com.au\/?p=582403","og:image":"https:\/\/www.vibewire.com.au\/wp-content\/uploads\/2026\/10\/Screenshot-2026-10-21-at-12.09.19-pm.png","og:image:secure_url":"https:\/\/www.vibewire.com.au\/wp-content\/uploads\/2026\/10\/Screenshot-2026-10-21-at-12.09.19-pm.png","og:image:width":"1066","og:image:height":"710","article:published_time":"2026-10-21T01:16:54+00:00","article:modified_time":"2026-10-21T01:16:58+00:00","twitter:card":"summary_large_image","twitter:site":"@VibewireCentral","twitter:title":"In Virginia, a data center ran diesel generators during a Code Red alert","twitter:description":"An on-site power failure at a Vantage Data Centers campus in Sterling, Virginia, led its backup diesel generators to run for nearly a full day during a Code Red air-quality alert.","twitter:creator":"@VibewireCentral","twitter:image":"https:\/\/www.vibewire.com.au\/wp-content\/uploads\/2026\/10\/Screenshot-2026-10-21-at-12.09.19-pm.png"},"aioseo_meta_data":{"post_id":"582403","title":"#post_title","description":null,"keywords":null,"keyphrases":{"focus":{"keyphrase":"Vantage Data Centres","score":0,"analysis":[]},"additional":[{"keyphrase":"Virginia","score":0},{"keyphrase":"USA","score":0},{"keyphrase":"Diesel Generators","score":0}]},"primary_term":null,"canonical_url":null,"og_title":"#post_title","og_description":"#post_excerpt","og_object_type":"default","og_image_type":"featured","og_image_url":"https:\/\/www.vibewire.com.au\/wp-content\/uploads\/2026\/10\/Screenshot-2026-10-21-at-12.09.19-pm.png","og_image_width":"1066","og_image_height":"710","og_image_custom_url":null,"og_image_custom_fields":null,"og_video":"","og_custom_url":null,"og_article_section":null,"og_article_tags":null,"twitter_use_og":true,"twitter_card":"default","twitter_image_type":"default","twitter_image_url":null,"twitter_image_custom_url":null,"twitter_image_custom_fields":null,"twitter_title":null,"twitter_description":null,"schema":{"blockGraphs":[],"customGraphs":[],"default":{"data":{"Article":[],"Course":[],"Dataset":[],"FAQPage":[],"Movie":[],"Person":[],"Product":[],"ProductReview":[],"Car":[],"Recipe":[],"Service":[],"SoftwareApplication":[],"WebPage":[]},"graphName":"BlogPosting","isEnabled":true},"graphs":[]},"schema_type":"default","schema_type_options":null,"pillar_content":false,"robots_default":true,"robots_noindex":false,"robots_noarchive":false,"robots_nosnippet":false,"robots_nofollow":false,"robots_noimageindex":false,"robots_noodp":false,"robots_notranslate":false,"robots_max_snippet":"-1","robots_max_videopreview":"-1","robots_max_imagepreview":"large","priority":null,"frequency":"default","local_seo":null,"seo_analyzer_scan_date":"2026-10-21 03:03:03","breadcrumb_settings":null,"limit_modified_date":false,"open_ai":null,"ai":{"faqs":[],"keyPoints":[],"schemas":[],"titles":[],"descriptions":[],"socialPosts":{"email":{"subject":"","preview":"","content":""},"linkedin":[],"twitter":[],"facebook":[],"instagram":[]}},"created":"2026-10-21 00:59:55","updated":"2026-10-21 03:03:03","focus_keyword":"Vantage Data Centres","additional_keywords":[{"word":"Virginia","score":78,"items":{"introductionKeyword":{"score":3},"keyphraseLength":{"score":9},"keyphraseDensity":{"score":9},"functionWordsInKeyphrase":{"score":9},"textCompetingLinks":{"score":9},"imageKeyphrase":{"score":3}}},{"word":"USA","score":69,"items":{"introductionKeyword":{"score":3},"keyphraseLength":{"score":9},"keyphraseDensity":{"score":4},"functionWordsInKeyphrase":{"score":9},"textCompetingLinks":{"score":9},"imageKeyphrase":{"score":3}}},{"word":"Diesel Generators","score":89,"items":{"introductionKeyword":{"score":9},"keyphraseLength":{"score":9},"keyphraseDensity":{"score":9},"functionWordsInKeyphrase":{"score":9},"textCompetingLinks":{"score":9},"imageKeyphrase":{"score":3}}}],"truseo_locale":null},"aioseo_breadcrumb":"<div class=\"aioseo-breadcrumbs\"><span class=\"aioseo-breadcrumb\">\n\t<a href=\"https:\/\/www.vibewire.com.au\/\" title=\"Home\">Home<\/a>\n<\/span><span class=\"aioseo-breadcrumb-separator\">\u00bb<\/span><span class=\"aioseo-breadcrumb\">\n\t<a href=\"https:\/\/www.vibewire.com.au\/?cat=12785\" title=\"Data Centre\">Data Centre<\/a>\n<\/span><span class=\"aioseo-breadcrumb-separator\">\u00bb<\/span><span class=\"aioseo-breadcrumb\">\n\tIn Virginia, a data center ran diesel generators during a Code Red alert\n<\/span><\/div>","aioseo_breadcrumb_json":[{"label":"Home","link":"https:\/\/www.vibewire.com.au\/"},{"label":"Data Centre","link":"https:\/\/www.vibewire.com.au\/?cat=12785"},{"label":"In Virginia, a data center ran diesel generators during a Code Red alert","link":"https:\/\/www.vibewire.com.au\/?p=582403"}],"_links":{"self":[{"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=\/wp\/v2\/posts\/582403","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=\/wp\/v2\/users\/90574"}],"replies":[{"embeddable":true,"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=%2Fwp%2Fv2%2Fcomments&post=582403"}],"version-history":[{"count":1,"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=\/wp\/v2\/posts\/582403\/revisions"}],"predecessor-version":[{"id":582560,"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=\/wp\/v2\/posts\/582403\/revisions\/582560"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=\/wp\/v2\/media\/582559"}],"wp:attachment":[{"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=%2Fwp%2Fv2%2Fmedia&parent=582403"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=%2Fwp%2Fv2%2Fcategories&post=582403"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.vibewire.com.au\/index.php?rest_route=%2Fwp%2Fv2%2Ftags&post=582403"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}